CR60 - Optimised circular fire damper 60-90'

Optimised circular fire damper with a minimum fire resistance of 60 minutes, available in small diameters (starting from 100 mm). A minimal pressure loss is guaranteed thanks to the thin blade, the fusible link aligned with the blade, and the transmission located outside the tunnel.

benefits

  • Easy to install
  • Optimal free air passage and minimal pressure loss
  • Optimal acoustic performance
  • Higher net building volume through compact size
  • Air-tightness class C according to EN1751

Features

  • Suitable for built-in and surface-mounted installation (kit CR-1s)
  • Suitable for installation remote from the wall
  • Minimal distance allowed
  • Suitable for rigid wall, rigid floor and light wall (metal stud gypsum plasterboard wall)
  • Sealing with fire resistant stone wool boards allowed, also for asymmetric opening
  • Tested according to EN 1366-2 up to 500 Pa
  • Operating mechanism outside the wall
  • Maintenance-free
  • For indoor use
  • Operating temperature: max. 50°C

Components

Components
  1. Casing in galvanised steel
  2. Damper blade
  3. Operating mechanism
  4. Rubber sealing ring
  5. Intumescent strip
  6. Base plate for thermo-electrical fuse
  7. Positioning plate
  8. Sealing ring for damper blade
  9. Fusible link
  10. Product identification