Download
Duct
Promatect L500 ≥ 30 mm
Gap between duct and damper (≤ 6 mm) sealed with refractory kit (on a depth ≥ 105 mm)
EI 60 (ve d hod i o) S 1500 AA multi
Download
Duct
Geoflam ≥ 30 mm
Gap between duct and damper (≤ 80 mm) sealed with refractory kit (on a depth ≥ 105 mm)
EI 60 (ve d hod i o) S 1500 AA multi
Download
Duct
Geotec ≥ 30 mm
Gap between duct and damper (≤ 80 mm) sealed with refractory kit (on a depth ≥ 105 mm)
EI 60 (ve d hod i o) S 1500 AA multi
Download
Duct
Tecniver ≥ 35 mm
Gap between duct and damper (≤ 6 mm) sealed with refractory kit (on a depth ≥ 105 mm)
EI 60 (ve d hod i o) S 1500 AA multi
Download
Duct
Glasroc F V500 ≥ 35 mm
Gap between duct and damper (≤ 6 mm) sealed with refractory kit (on a depth ≥ 105 mm)
EI 60 (ve d hod i o) S 1500 AA multi
Download
Duct
Exthamat ≥ 25 mm
Gap between duct and damper (≤ 80 mm) sealed with refractory kit (on a depth ≥ 105 mm)
EI 60 (ve d hod i o) S 1500 AA multi
Download
Duct
Desenfire HD ≥ 25 mm
Gap between duct and damper (≤ 80 mm) sealed with refractory kit (on a depth ≥ 105 mm)
EI 60 (ve d hod i o) S 1500 AA multi
Download
Duct
Promatect L500 ≥ 40 mm
Gap between duct and damper (≤ 6 mm) sealed with refractory kit (on a depth ≥ 105 mm)
EI 90 (ve d hod i o) S 1500 AA multi
Download
Duct
Geoflam ≥ 35 mm
Gap between duct and damper (≤ 80 mm) sealed with refractory kit (on a depth ≥ 105 mm)
EI 90 (ve d hod i o) S 1500 AA multi
Download
Duct
Tecniver ≥ 45 mm
Gap between duct and damper (≤ 6 mm) sealed with refractory kit (on a depth ≥ 105 mm)
EI 90 (ve d hod i o) S 1500 AA multi
Download
Duct
Exthamat ≥ 30 mm
Gap between duct and damper (≤ 80 mm) sealed with refractory kit (on a depth ≥ 105 mm)
EI 90 (ve d hod i o) S 1500 AA multi
Duct
Desenfire THD ≥ 25 mm
Gap between duct and damper (≤ 80 mm) sealed with refractory kit (on a depth ≥ 105 mm)
EI 90 (ve d hod i o) S 1500 AA multi
Download
Shaft
Reinforced concrete (≥ 2150 kg/m³) ≥ 70 mm
Mortar
EI 90 (ve d i o) S 1500 AA multi
Download
Duct
Promatect L500 ≥ 50 mm
Gap between duct and damper (≤ 6 mm) sealed with refractory kit (on a depth ≥ 105 mm)
EI 120 (ve d hod i o) S 1500 AA multi
Download
Duct
Geoflam ≥ 45 mm
Gap between duct and damper (≤ 80 mm) sealed with refractory kit (on a depth ≥ 105 mm)
EI 120 (ve d hod i o) S 1500 AA multi
Download
Duct
Geoflam Light ≥ 35 mm
Gap between duct and damper (≤ 80 mm) sealed with refractory kit (on a depth ≥ 105 mm)
EI 120 (ve d hod i o) S 1500 AA multi
Download
Duct
Geotec ≥ 45 mm
Gap between duct and damper (≤ 80 mm) sealed with refractory kit (on a depth ≥ 105 mm)
EI 120 (ve d hod i o) S 1500 AA multi
Download
Duct
Tecniver ≥ 50 mm
Gap between duct and damper (≤ 6 mm) sealed with refractory kit (on a depth ≥ 105 mm)
EI 120 (ve d hod i o) S 1500 AA multi
Download
Duct
Glasroc F V500 ≥ 50 mm
Gap between duct and damper (≤ 6 mm) sealed with refractory kit (on a depth ≥ 105 mm)
EI 120 (ve d hod i o) S 1500 AA multi
Download
Duct
Exthamat ≥ 35 mm
Gap between duct and damper (≤ 80 mm) sealed with refractory kit (on a depth ≥ 105 mm)
EI 120 (ve d hod i o) S 1500 AA multi
Download
Duct
Desenfire HD ≥ 35 mm
Gap between duct and damper (≤ 80 mm) sealed with refractory kit (on a depth ≥ 105 mm)
EI 120 (ve d hod i o) S 1500 AA multi
Duct
Desenfire STR ≥ 25 mm
Gap between duct and damper (≤ 80 mm) sealed with refractory kit (on a depth ≥ 105 mm)
EI 120 (ve d hod i o) S 1500 AA multi
Download
Shaft
Masonry, concrete blocks, concrete ≥ 100 mm
Mortar
EI 120 (ve d i o) S 1500 AA multi