AVANTAGE 1V120 - Installation

Operation: opening

1
Unlocking 1V
Manual:
Insert the key in the lock. Turn the key 20° anti-clockwise: the shutter opens. Remove the key from the lock.
Remote:
Remote controlled by an electrical impulse or by interrupting the magnet's power supply (option VD/VM).
2
Unlocking 2V
Manual:
Insert the key in the lock. Turn the key 20° anti-clockwise: the shutter opens. Remove the key from the lock.
Remote:
Remote controlled by an electrical impulse or by interrupting the magnet's power supply (option VD/VM).

Operation: closing

1
Resetting 1V
Manual:
Turn the key 20° clock wise and withdraw it. Push the blocking mechanism. Close the shutter by pulling the metal profile.
2
Resetting 2V
Manual:
Press on both blocking devices to deactivate them.
3
Turn the key 20° clock wise and withdraw it. Close both shutters together by pulling on the metal profiles. Make sure that the shutters hook in each other as illustrated.
4
Resetting ME
Manual:
Turn the key 20° clock wise and withdraw it. Push the blocking mechanism. Close the shutter by pulling the metal profile.
Remote:
Power the actuator for at least 90 sec. (respect the prescribed voltage 24 or 48 Vdc).
The resetting stops automatically when the shutter is closed.
Switch off the power supply for at least 90 sec. in between each resetting cycle.

Electrical wiring

1
The electrical supply can be done at the 4 corners of the shutter.
2
Drill a hole in the refractory material at the chosen corner(s). The galvanised part at the inside of the shutter is already indented.
Caution: after passing and fixing the cables, you need to seal the drilled hole in the refractory plates around the electrical cables with fire resistant adhesive sealant (BCM f.e.).
3
Pierce an opening in the connection box. Affix the grommet delivered with the product.
4
Lead the cables through the opening. Use the protective sleeve (1), the fixation clips (2) and the plastic cable clamp (3) to attach the cables to the frame. Lead the cables to the connection box through the grommet (4) and connect according to the electrical connection diagram.
Comply with the installation rules according to article 6.1 of NF S 61-932.

Position in the shaft

1
The shutter is affixed to the smoke control duct through a sleeve. That sleeve can be installed either in the duct, in the axis of the duct or outside the duct (or duct extension).

Shock absorbers for the doors

1
Shock absorbers (foam) come standard with the shutter. They can be affixed to the inner face of the door to prevent it from hitting the shaft wall when opening.
2
Be sure to cut these blocks to the correct dimensions so that the blocking mechanism can engage when the door opens.

Installation into vertical concrete shaft with mounting frame

The product was tested and approved in:
  • Concrete ≥ 70 mm | EI 90 (ved i o) S 1500 AA multi | Avantage 120 | Type of installation: in duct/shaft-mounted 0/180°. Minimal in-between distances authorised. | 300x385 mm ≤ Avantage 1V ≤ 700x1075 mm; 350x385 mm ≤ Avantage 2V ≤ 1100x1105 mm; 350x385 mm ≤ Avantage 1V ME ≤ 700x1075 mm
1
In case the mounting frame is screwed:
Make an opening with dimensions (W+20) x (H+20) mm.
In case the mounting frame is fixed with mortar:
Make an opening with dimensions (W+20) x (H+20) mm till (W+100) x (H+100) mm.
2
The mounting frame should always be fastened to the concrete shaft with screws and dowels (Ø 6 x minimum 60 mm, steel or stainless steel).
For an opening with dimensions up to (W+20) x (H+20) mm:
Two fixing lugs are provided at the bottom and at the top of the mounting frame: fold these against the shaft and fasten the mounting frame with 4 screws Ø 6 x 60 mm, taking care not to misshape it. These screws can be inserted through any of the punched holes in the lugs, depending on the thickness of the shaft wall. The finished opening must have the same size as the mounting frame (W+10) x (H+10) mm.
For an opening with dimensions up to (W+100) x (H+100) mm:
Apply mortar around the opening to reduce the opening to the outer dimensions of the frame, then proceed as mentioned above to fasten the frame into the opening. Make sure that the gap between the frame and the opening is sealed completely with mortar.
The mortar must harden completely before the damper is fastened to the mounting frame.
3
Put aside the screws that are affixed to one of the cross slats, then unscrew the 4 cross slats of the mounting frame and fold the 8 fastening plates in the frame.
4
Rotate the four fastening plates on the damper 90° (to the upright position).
5
Open and position the shutter in the mounting frame. If VM magnet: remove the key from the lock to open the shutter.
Fasten the shutter onto the mounting frame with the 4 screws supplied, as shown in the drawing. Tightening the screws pulls the shutter towards the wall until its final position. You can also slightly correct the angle of the shutter with respect to the mounting frame.
Connect the mechanism according to the wiring diagram.
Check the mobility of the shutter.

Installation into vertical concrete shaft without mounting frame

The product was tested and approved in:
  • Concrete ≥ 70 mm | EI 90 (ved i o) S 1500 AA multi | Avantage 120 | Type of installation: in duct/shaft-mounted 0/180°. Minimal in-between distances authorised. | 300x385 mm ≤ Avantage 1V ≤ 700x1075 mm; 350x385 mm ≤ Avantage 2V ≤ 1100x1105 mm; 350x385 mm ≤ Avantage 1V ME ≤ 700x1075 mm
1
Rotate the four fastening plates on the damper 90° (to the upright position).
The fastening plates are not used for an installation without a mounting frame.
2
Make an opening with dimensions (W+10) x (H+10) mm.
Open and position the shutter in the opening. If VM magnet: remove the key from the lock to open the shutter.
Fix the shutter in the opening using 4 screws and dowels Ø6 x 40 mm.
Connect the mechanism according to the wiring diagram.
Check the mobility of the shutter.

Installation into vertical duct with built-in mounting frame: general instructions for all types of shafts (other than concrete)

1
Make an opening with dimensions (W+A) x (H+A) mm. A = 2 x thickness sleeve (e) + 20 mm .
Fit a sleeve of the same type and thickness of the duct (thickness e) of minimum 105 mm deep in the opening.
See details per type of shaft hereafter.
2
Fasten and seal the mounting frame. See details per type of duct hereafter.
Two fixing lugs are provided at the bottom and at the top of the mounting frame: fold these against the sleeve. When fixed with screws, fasten the mounting frame to the sleeve with chipboard screws (Ø 6 x e) mm. These screws can be fixed in one of the openings provided for this purpose, depending on the depth of the sleeve.
Take care not to misshape the frame during its installation. The finished opening must have the same size as the mounting frame (W+10) x (H+10) mm.
3
Put aside the screws that are affixed to one of the cross slats, then unscrew the 4 cross slats of the mounting frame and fold the 8 fastening plates in the frame.
4
Rotate the four fastening plates on the damper 90° (to the upright position).
5
Open and position the shutter in the mounting frame. If VM magnet: remove the key from the lock to open the shutter.
Fasten the shutter onto the mounting frame with the 4 screws supplied, as shown in the drawing. Tightening the screws pulls the shutter towards the wall until its final position. You can also slightly correct the angle of the shutter with respect to the mounting frame.
Connect the mechanism according to the wiring diagram.
Check the mobility of the shutter.

Installation into vertical duct (without a mounting frame): general instructions for all types of shafts (other than concrete)

1
Rotate the four fastening plates on the damper 90° (to the upright position).
The fastening plates are not used for an installation without a mounting frame.
2
Make an opening with dimensions (W+A) x (H+A) mm. A = 2 x thickness sleeve (e) + 10 mm.
Fit a sleeve of the same type and thickness of the duct (thickness e) of minimum 105 mm deep in the opening.
Open and position the shutter in the opening. If VM magnet: remove the key from the lock to open the shutter.
Fix the shutter in the opening using 4 screws Ø6 x 40 mm.
Caution: make sure that the screws don't exceed the sleeve's thickness!
Connect the mechanism according to the wiring diagram.
Check the mobility of the shutter.

Installation into vertical duct PROMATECT L500

The product was tested and approved in:
  • Promatect L500 ≥ 40 mm | EI 90 (ved i o) S 1500 AA multi | Avantage 120 | Type of installation: in duct/shaft-mounted 0/180°. Minimal in-between distances authorised. | 300x385 mm ≤ Avantage 1V ≤ 700x1075 mm; 350x385 mm ≤ Avantage 2V ≤ 1100x1105 mm; 350x385 mm ≤ Avantage 1V ME ≤ 700x1075 mm
  • Promatect L500 ≥ 50 mm | EI 120 (ved i o) S 1500 AA multi | Avantage 120 | Type of installation: in duct/shaft-mounted 0/180°. Minimal in-between distances authorised. | 300x385 mm ≤ Avantage 1V ≤ 700x1075 mm; 350x385 mm ≤ Avantage 2V ≤ 1100x1105 mm; 350x385 mm ≤ Avantage 1V ME ≤ 700x1075 mm
1
Installation with mounting frame:
Assemble the sleeve with staples and affix the assembled sleeve to the duct wall with staples.
Coat the edges of the opening with adhesive plaster type Promacol S.
Seal the mounting frame with Promacol S taking care not to misshape it.
2
Installation without mounting frame:
Assemble the sleeve with staples and affix the assembled sleeve to the duct wall with staples.

Installation into vertical duct GEOFLAM (LIGHT) / GEOTEC

The product was tested and approved in:
  • Geoflam ≥ 35 mm | EI 90 (ved i o) S 1500 AA multi | Avantage 120 | Type of installation: in duct/shaft-mounted 0/180°. Minimal in-between distances authorised. | 300x385 mm ≤ Avantage 1V ≤ 700x1075 mm; 350x385 mm ≤ Avantage 2V ≤ 1100x1105 mm; 350x385 mm ≤ Avantage 1V ME ≤ 700x1075 mm
  • Geoflam ≥ 45 mm | EI 120 (ved i o) S 1500 AA multi | Avantage 120 | Type of installation: in duct/shaft-mounted 0/180°. Minimal in-between distances authorised. | 300x385 mm ≤ Avantage 1V ≤ 700x1075 mm; 350x385 mm ≤ Avantage 2V ≤ 1100x1105 mm; 350x385 mm ≤ Avantage 1V ME ≤ 700x1075 mm
  • Geoflam Light ≥ 35 mm | EI 120 (ved i o) S 1500 AA multi | Avantage 120 | Type of installation: in duct/shaft-mounted 0/180°. Minimal in-between distances authorised. | 300x385 mm ≤ Avantage 1V ≤ 700x1075 mm; 350x385 mm ≤ Avantage 2V ≤ 1100x1105 mm; 350x385 mm ≤ Avantage 1V ME ≤ 700x1075 mm
  • Geotec ≥ 45 mm | EI 120 (ved i o) S 1500 AA multi | Avantage 120 | Type of installation: in duct/shaft-mounted 0/180°. Minimal in-between distances authorised. | 300x385 mm ≤ Avantage 1V ≤ 700x1075 mm; 350x385 mm ≤ Avantage 2V ≤ 1100x1105 mm; 350x385 mm ≤ Avantage 1V ME ≤ 700x1075 mm
1
Installation with mounting frame:
Coat the edges of the opening with adhesive plaster type PLACOL (in case of Geoflam) or GEOCOL (S) (in case of Geotec).
In case of Geotec you can also assemble the sleeve with glue and screws Ø 5 x (2 x e) mm and affix the assembled sleeve to the duct wall with glue and screws Ø 5 x (2 x e) mm every 100 mm.
Seal the joints between uprights and cross pieces and between the lining and the wall with vegetable fibre caulking and plaster or with GEOCOL (S) (in case of Geotec).
Two fixing lugs are provided at the bottom and at the top of the mounting frame: fold these against the sleeve. Caulk the mounting frame to the duct with vegetable fibre or (in case of Geotec) you can also coat the opening with Geocol (S) and fasten the mounting frame with screws of Ø 5 x e mm. Take care not to misshape the frame. The finished opening must have the same size as the mounting frame (W+10) x (H+10) mm.
2
Installation without mounting frame:
Coat the edges of the opening with adhesive plaster type PLACOL (in case of Geoflam) or GEOCOL (S) (in case of Geotec).
Seal the joints between uprights and cross pieces and between the lining and the wall with vegetable fibre caulking and plaster or with GEOCOL (S) (in case of Geotec).
In case of Geotec you can also assemble the sleeve with glue and screws Ø 5 x (2 x e) mm and affix the assembled sleeve to the duct wall with glue and screws Ø 5 x (2 x e) mm every 100 mm.

Installation into vertical duct TECNIVER

The product was tested and approved in:
  • Tecniver ≥ 45 mm | EI 90 (ved i o) S 1500 AA multi | Avantage 120 | Type of installation: in duct/shaft-mounted 0/180°. Minimal in-between distances authorised. | 300x385 mm ≤ Avantage 1V ≤ 700x1075 mm; 350x385 mm ≤ Avantage 2V ≤ 1100x1105 mm; 350x385 mm ≤ Avantage 1V ME ≤ 700x1075 mm
  • Tecniver ≥ 50 mm | EI 120 (ved i o) S 1500 AA multi | Avantage 120 | Type of installation: in duct/shaft-mounted 0/180°. Minimal in-between distances authorised. | 300x385 mm ≤ Avantage 1V ≤ 700x1075 mm; 350x385 mm ≤ Avantage 2V ≤ 1100x1105 mm; 350x385 mm ≤ Avantage 1V ME ≤ 700x1075 mm
1
Installation with mounting frame:
Put glue type CF GLUE on the uprights and cross pieces and between the lining and the wall. Screw the sleeve using chipboard screws Ø5 x 70 mm at 150 mm intervals.
Two fixing lugs are provided at the bottom and at the top of the mounting frame: fold these against the sleeve. First coat the opening with glue CF GLUE. Glue the mounting frame to the lining taking care not to misshape it. The finished opening must have the same size as the mounting frame (W+10) x (H+10) mm.
2
Installation without mounting frame:
Put glue type CF GLUE on the uprights and cross pieces and between the lining and the wall. Screw the sleeve using chipboard screws Ø5 x 70 mm at 150 mm intervals.

Installation into vertical duct GLASROC F V500

The product was tested and approved in:
  • Glasroc F V500 ≥ 50 mm | EI 120 (ved i o) S 1500 AA multi | Avantage 120 | Type of installation: in duct/shaft-mounted 0/180°. Minimal in-between distances authorised. | 300x385 mm ≤ Avantage 1V ≤ 700x1075 mm; 350x385 mm ≤ Avantage 2V ≤ 1100x1105 mm; 350x385 mm ≤ Avantage 1V ME ≤ 700x1075 mm
1
Installation with mounting frame:
Put glue type GLASROC F V500 on the uprights and cross pieces and between the lining and the wall. Screw the sleeve using chipboard screws Ø5 x 70 mm at 150 mm intervals.
Two fixing lugs are provided at the bottom and at the top of the mounting frame: fold these against the sleeve. First coat the opening with glue GLASROC F V500. Glue the mounting frame to the lining taking care not to misshape it. The finished opening must have the same size as the mounting frame (W+10) x (H+10) mm.
2
Installation without mounting frame:
Put glue type GLASROC F V500 on the uprights and cross pieces and between the lining and the wall. Screw the sleeve using chipboard screws Ø5 x 70 mm at 150 mm intervals.

Installation into vertical duct EXTHAMAT

The product was tested and approved in:
  • Exthamat ≥ 35 mm | EI 120 (ved i o) S 1500 AA multi | Avantage 120 | Type of installation: in duct/shaft-mounted 0/180°. Minimal in-between distances authorised. | 300x385 mm ≤ Avantage 1V ≤ 700x1075 mm; 350x385 mm ≤ Avantage 2V ≤ 1100x1105 mm; 350x385 mm ≤ Avantage 1V ME ≤ 700x1075 mm
  • Exthamat ≥ 30 mm | EI 90 (ved i o) S 1500 AA multi | Avantage 120 | Type of installation: in duct/shaft-mounted 0/180°. Minimal in-between distances authorised. | 300x385 mm ≤ Avantage 1V ≤ 700x1075 mm; 350x385 mm ≤ Avantage 2V ≤ 1100x1105 mm; 350x385 mm ≤ Avantage 1V ME ≤ 700x1075 mm
1
Installation with mounting frame:
Coat the edges of the opening with adhesive plaster.
Seal the joints between uprights and cross pieces and between the lining and the wall with vegetable fibre caulking and plaster.
Two fixing lugs are provided at the bottom and at the top of the mounting frame: fold these against the sleeve. Caulk the mounting frame to the duct with vegetable fiber caulking and plaster and taking care not to misshape it. The finished opening must have the same size as the mounting frame (W+10) x (H+10) mm.
Coat the edges of the opening with adhesive plaster.
2
Installation without mounting frame:
Coat the edges of the opening with adhesive plaster.
Seal the joints between uprights and cross pieces and between the lining and the wall with vegetable fibre caulking and plaster.

Installation into vertical duct DESENFIRE (HD/THD/STR)

The product was tested and approved in:
  • Desenfire HD ≥ 35 mm | EI 120 (ved i o) S 1500 AA multi | Avantage 120 | Type of installation: in duct/shaft-mounted 0/180°. Minimal in-between distances authorised. | 300x385 mm ≤ Avantage 1V ≤ 700x1075 mm; 350x385 mm ≤ Avantage 2V ≤ 1100x1105 mm; 350x385 mm ≤ Avantage 1V ME ≤ 700x1075 mm
  • Desenfire ≥ 45 mm | EI 120 (ved i o) S 1500 AA multi | Avantage 120 | Type of installation: in duct/shaft-mounted 0/180°. Minimal in-between distances authorised. | 300x385 mm ≤ Avantage 1V ≤ 700x1075 mm; 350x385 mm ≤ Avantage 2V ≤ 1100x1105 mm; 350x385 mm ≤ Avantage 1V ME ≤ 700x1075 mm
  • Desenfire THD ≥ 25 mm | EI 90 (ved i o) S 1500 AA multi | Avantage 120 | Type of installation: in duct/shaft-mounted 0/180°. Minimal in-between distances authorised. | 300x385 mm ≤ Avantage 1V ≤ 700x1075 mm; 350x385 mm ≤ Avantage 2V ≤ 1100x1105 mm; 350x385 mm ≤ Avantage 1V ME ≤ 700x1075 mm
1
Installation with mounting frame:
Coat the edges of the opening with adhesive plaster, type FACILIS.
Seal the joints between uprights and cross pieces and between the lining and the wall with vegetable fibre caulking and plaster.
Two fixing lugs are provided at the bottom and at the top of the mounting frame: fold these against the sleeve. Caulk the mounting frame to the duct with vegetable fiber caulking and plaster and taking care not to misshape it. The finished opening must have the same size as the mounting frame (W+10) x (H+10) mm.
2
Installation without mounting frame:
Coat the edges of the opening with adhesive plaster, type FACILIS.
Seal the joints between uprights and cross pieces and between the lining and the wall with vegetable fibre caulking and plaster.

Installation at minimal distances

1
The shutters can be installed at minimal distance on top of or next to each other, if they are mounted in separate sleeves made from the duct material with the required fire resistance. It is advised not to exceed a 4 x 2 configuration (W x H).
2
In case several shutters are mounted at a minimal distance, the bearing and reinforcement points of the duct must be adjusted in proportion to the increased weight. The installation of the duct must comply with the classification report delivered by the duct manufacturer.
3
When mounting in a concrete shaft, you need to provide a continuous reinforcement in the vertical columns of at least 4 x Ø 8 mm.

General remarks

  • The installation must comply with the installation manual and the classification report.
  • The installation of the smoke control duct must comply with the classification report delivered by the manufacturer.
  • Axis orientation: see the declaration of performance.
  • Avoid the obstruction of adjoining smoke control ducts.
  • Verify if the blade can move freely.
  • Rf-t smoke dampers may be applied to smoke control ducts that have been tested according to EN 1366-8 and EN 1366-9 as appropriate, constructed from similar materials with a fire resistance, thickness and density equal or superior to these of the tested materials.
  • Caution: when fitting, the product should be handled with care and remain protected from any sealing products.
  • Caution: before putting the installation into operation, clean off all the dust and dirt.
  • Caution: bear in mind the blade’s clearance inside the smoke control duct.