VRE - Mechanisms

BEN - Remotely controlled servomotor

The BEN servomotor is specifically designed for remote control of smoke control dampers.
  1. Access for manual operation
  2. Plug (ST)

Variants

  • BEN24
    Servomotor BEN 24V
  • BEN230
    Servomotor BEN 230V

Unlocking

  • manual unlocking
    turn the enclosed handle anticlockwise (VRE; VU120) or clockwise (MARKAGE MB; VUW120).
  • remote unlocking
    power cables 1 and 2.

Resetting

  • manual resetting
    turn the enclosed handle clockwise (VRE; VU120) or anticlockwise (MARKAGE MB; VUW120).
  • motorised resetting
    power cables 1 and 3.

BEE - Remotely controlled servomotor

The BEE servomotor is specifically designed for remote control of smoke control dampers.
  1. Access for manual operation
  2. Plug (ST)

Variants

  • BEE24
    Servomotor BEE 24V
  • BEE230
    Servomotor BEE 230V

Unlocking

  • manual unlocking
    turn the enclosed handle anticlockwise (VRE) or clockwise (MARKAGE MB).
  • remote unlocking
    power cables 1 and 2.

Resetting

  • manual resetting
    turn the enclosed handle clockwise (VRE) or anticlockwise (MARKAGE MB).
  • motorised resetting
    power cables 1 and 3.

BEE-SR-10V - Remotely controlled modulating actuator

The BEE-SR-10V modulating actuator is specifically designed for remote control of smoke control dampers. The position of the damper blade is adjustable by means of a 0 to 10 V connection.
  1. Access for manual operation

Variants

  • BEE24-SR-10V
    Modulating actuator BEE24-SR-10V for the control of the airflow

Unlocking

  • manual unlocking
    turn the enclosed handle anti-clockwise.
  • remote unlocking
    apply 10 V to cable 3.

Resetting

  • manual resetting
    turn the enclosed handle clockwise.
  • motorised resetting
    apply (0)2 V to cable 3.

BEE-SR-0V - Remotely controlled modulating actuator

The BEE-SR-0V modulating actuator is specifically designed for remote control of smoke control dampers. The position of the damper blade is adjustable by means of a 0 to 10 V connection.
  1. Access for manual operation

Variants

  • BEE24-SR-0V
    Modulating actuator BEE24-SR-0V for the control of the airflow

Unlocking

  • manual unlocking
    turn the enclosed handle anti-clockwise.
  • remote unlocking
    apply (0)2 V to cable 3.

Resetting

  • manual resetting
    turn the enclosed handle clockwise.
  • motorised resetting
    apply 10 V to cable 3.