VU120 - Mechanisms

BEN - Remotely controlled servomotor

The BEN servomotor is specifically designed for remote control of smoke control dampers.
  1. Access for manual operation
  2. Plug (ST)

Variants

  • BEN24
    Servomotor BEN 24V
  • BEN230
    Servomotor BEN 230V
  • BEN24-ST
    Servomotor BEN 24V with plug (ST)

Unlocking

  • manual unlocking
    turn the enclosed handle anticlockwise (VRE; VU120) or clockwise (MARKAGE MB; VUW120).
  • remote unlocking
    power cables 1 and 2.

Resetting

  • manual resetting
    turn the enclosed handle clockwise (VRE; VU120) or anticlockwise (MARKAGE MB; VUW120).
  • motorised resetting
    power cables 1 and 3.

MANF - Upgradeable remote controlled unlocking mechanism

The unlocking mechanism MANF EVO unlatches the damper blade via remote control by sending an electric impulse (VD) or by interrruption (VM) of the magnets power supply. A begin- and end of range switch (FDCU) is standard available. The blade can be reset manually (MANF EVO) or by an electric motor ME (option and kit).
  1. Unlocking button
  2. Resetting handle
  3. Cable entrance

Variants

  • MANF EVO
    Upgradeable remote controlled unlocking mechanism

Options - magnet

  • VD24
    Natural magnet 24 V DC + FDCU
  • VD48
    Natural magnet 48 V DC + FDCU
  • VM24
    Electromagnet 24 V DC + FDCU
  • VM48
    Electromagnet 48 V DC + FDCU

Options - motor

  • ME
    Resetting motor ME 24V/48V

Options - Switch

  • FDCU
    Limit switch 'open/closed'
  • FDCB
    Auxiliary limit switch 'open/closed'

Unlocking

  • manual unlocking
    use the unlocking button (1).
  • automatic unlocking
    n/a
  • remote unlocking
    (option VD/VM MAN EVO FDCU) by sending an electrical impulse (VD) or by interrupting the power supply (VM) to the magnet's entrance.

Resetting

  • manual resetting
    turn 90° counter-clockwise with a hex socket wrench 13 mm (2).
  • motorised resetting
    (option ME MANF) switch off the power supply for at least 10 sec. Power the actuator for at least 30 sec. (respect the prescribed voltage and polarity). The resetting stops automatically if a torque > 20 Nm is detected.

Documents Scroll down/right to view the entire table

File Type Format Date
Technical product brochure KIT FDCB_MANTechnical datasheet KITpdf [6,078.29 kB]14/02/2014
Technical product brochure KIT FDCU_MANTechnical datasheet KITpdf [7,085.53 kB]14/02/2014
Technical product brochure KIT MANF_EVOTechnical datasheet KITpdf [4,677.36 kB]14/03/2019
Technical product brochure KIT ME_MANF_EVOTechnical datasheet KITpdf [1,063.67 kB]08/05/2012
Technical product brochure KIT V_MAN_EVO_FDCUTechnical datasheet KITpdf [5,428.51 kB]14/02/2014

NF - Remotely controlled spring return actuator (for small dimensions)

The servomotor is designed to control smoke control dampers from a distance. This solution is suitable in case of counter-pressure. Beginning and end of range switches included.
  1. Access for manual resetting
  2. Locking button

Variants

  • NF24
    Actuator NF 24V
  • NF230
    Actuator NF 230V

Unlocking

  • manual unlocking
    use the enclosed handle and turn 1/4 turn counter-clockwise; push the locking button to the left.
  • automatic unlocking
    n/a
  • remote unlocking
    by interrupting the power supply (for dampers with NF/SF-VD module: by sending an electrical impulse).

Resetting

  • manual resetting
    use the enclosed handle and turn counterclockwise. To block the motor, push the locking button to the right.
  • motorised resetting
    switch off the power supply for at least 10 sec (3 sec for NF/SF-VD module). Supply the actuator (respect the prescribed voltage) for at least 180 sec. The resetting stops automatically when the end of range is reached (damper closed).

Documents Scroll down/right to view the entire table

File Type Format Date
Technical product brochure KIT SF_NFTechnical datasheet KITpdf [371.70 kB]19/11/2015

SF - Remotely controlled spring return actuator (for large dimensions)

The servomotor is designed to control smoke control dampers from a distance. This solution is suitable for use in case of counter-pressure. Beginning and end of range switches included.
  1. Access for manual resetting
  2. Locking button

Variants

  • SF24
    Actuator SF 24V
  • SF230
    Actuator SF 230V

Unlocking

  • manual unlocking
    use the enclosed handle and turn 1/4 turn counter-clockwise; push the locking button to the left.
  • automatic unlocking
    n/a
  • remote unlocking
    by interrupting the power supply (for dampers with NF/SF-VD module: by sending an electrical impulse).

Resetting

  • manual resetting
    use the enclosed handle and turn counterclockwise. To block the motor, push the locking button to the right.
  • motorised resetting
    switch off the power supply for at least 10 sec (3 sec for NF/SF-VD module). Supply the actuator (respect the prescribed voltage) for at least 180 sec. The resetting stops automatically when the end of range is reached (damper closed).

Documents Scroll down/right to view the entire table

File Type Format Date
Technical product brochure KIT SF_NFTechnical datasheet KITpdf [371.70 kB]19/11/2015